• ABout TOPP

30V50Ah DC Power System

30V50Ah DC Power System

The composition of the DC power system

*Rectifier module
*Battery system
*Comprehensive detection unit
*Centralized monitoring module
*Other components

图片1(18)

The work principle of the DC system

AC normal working condition:

When the AC input of the system supplies power normally, the AC power distribution unit supplies power to each rectifier module. The high-frequency rectification module converts AC power into DC power, and outputs it through a protective device (fuse or circuit breaker). On the one hand, it charges the battery pack, and on the other hand, it provides normal working power to the DC load through the DC power distribution feed unit.

AC power loss working state:

When the system's AC input fails and the power is cut off, the rectifier module stops working, and the battery supplies power to the DC load without interruption. The monitoring module monitors the discharge voltage and current of the battery in real time, and when the battery discharges to the set end voltage, the monitoring module gives an alarm. At the same time, the monitoring module displays and processes the data uploaded by the power distribution monitoring circuit at all times.

图片2

Battery System

Battery Cell

图片1(9)
图片5

Battery cell data sheet

No. Item Parameters
1 Nominal voltage 3.2V
2 Nominal capacity 50Ah
3 Rated working current 25A(0.5C)
4 Max. charging voltage 3.65V
5 Min. discharge voltage 2.0V
6 Max Pulse charge current 2C ≤10s
7 Max Pulse discharge current 3C ≤10s
8 AC internal resistance ≤1.0mΩ (AC Impedance, 1000 Hz)
9 Self-discharge ≤3%
10 Weight 1.12±0.05kg
11 Dimensions 148.2*135*27mm

Battery Pack

图片4
图片1(10)

Battery pack data sheet

No. Item Parameters
1 Battery type Lithium iron phosphate(LiFePO4)
2 Nominal voltage 32V
3 Rated capacity 50Ah @0.3C3A,25℃
4 Operating current 25Amps
5 Peak current 50Amps
6 Operating voltage DC 25~36.5V
7 Charge current 25Amps
8 Assembly 10S1P
9 Boxmaterial Steel plate
10 Dimensions 290(L)*150(W)*150(H)mm
11 Weight About 14 kg
12 Operating temperature - 20 ℃to 60 ℃
13 Chargetemperature 0 ℃to 45 ℃
14 Storage temperature - 10 ℃to 45 ℃

BMS Electrical Parameters

Technology Name Common parameters
Charge and discharge withstand voltage 100V
communication method Bluetooth, RS485 , Serial port , CAN GPS
Number of battery strings 9-15 skewers
Cell Type Ternary lithium battery, lithium iron phosphate, lithium titanate
Temperature number 3​
Balance current 120mA
voltage range 0.5V – 5V
Voltage accuracy 0.5 % ( 0 ℃ - 80 ℃ ) , 0.8 % ( -40 ℃ - 0 ℃ )​​​​​​
temperature range -40 ℃ - 80 ℃
Current range -100A – 100A ( determined by the model of the same series product)
Current accuracy 2% (-100A – 100A)
CAN communication Support CANOPEN , CAN customization
RS485 Isolation, modbus protocol
Manual wake-up support
Charging wake-up support
Bluetooth Support Android APP , Apple mobile phone APP
Low battery indicator Low battery alarm IO output
SOC Accuracy <5%
B- Drop protection not support
Operating power consumption 20mA
Standby power consumption 2mA
Storage and transportation power consumption 40uA
Event Storage 120 loop event records
Status Indicator 2 LED status lights
Battery indicator Support 5 -grid power display, 4 -grid power display and LCD digital display
storage temperature -20 ℃ - 60 ℃
0V charging Does not support 0V charging
Hibernation Description BMSAutomatic standby conditions :The automatic sleep function is set to on. When the battery is not charged or discharged, there is no communication, no Bluetooth link, and no balancing.
30 S (time can be adjusted by the host computer ), thenBMS Enter standby mode.the BMS automatically enters standby mode, the charge and discharge ports remain in the closed state (powered ) .

 

How to connect the BMS

图片1(11)

 

30V DC Power Rectifier-Technical parameters

Input characteristics

Input voltage range 120 ~ 370VDC
Frequency range 47 ~ 63Hz
Alternating current 3.6A/230VAC
Inrush current 70A/230VAC
Efficiency 89%
Power factor PF>0.93/230VAC (full load)
Leakage Current <1.2mA / 240VAC

 

Output characteristics

Power Rectifier function:1. DC OK signal PSU on: 3.3 ~ 5.6V; PSU off: 0 ~ 1V2. Fan control When the load is 35±15% or RTH2≧50℃, the fan turns on

Output voltage range 28.8 ~ 39.6V
Regulation ±1.0%
Ripple & Noise (Max.) 200mVp-p
Voltage Tolerance Limit ±5%
Start-up, rise time 1,800 ms, 50ms / 230VAC(Full load)
Rated current 17.5A
Max transient current >32A
Charging Hours after battery total discharged <3Hours
DC Voltage 36V
Rated Power 630W
Proposed Standing load <360W

Power Rectifier Protect function:

1. Overload protection 105%~135% of rated output power Protection mode: constant current limit, automatically recovers after abnormal load conditions are removed
2. Overvoltage protection 41.4~48.6V Protection mode: shut down output, normal output can be restored after power is restarted
3. Overtemperature protection shuts down output, and automatically recovers after temperature drops

Power Rectifier Working Graph

图片1(13)

Ambient temperature (℃)

图片1(12)

Input voltage(V)60Hz

Monitoring System

Introduction

Cyclone monitors use a human-machine interface, an electric power operation power supply monitoring system composed of an mcgsTpc embedded integrated touch screen and a detection unit. The main monitor is composed of the UM series monitors representing our company's core technology, suitable for DC systems below 1000AH, completing charge and discharge management and various monitoring tasks, and can form electric power operation power supply systems of various voltage levels in conjunction with various charging modules produced by our company. Cyclone monitors all have reliable background communication functions, and are particularly suitable for unattended and automatic operation occasions.

Basic configuration:

*Human-machine interface: TPC 70 22 ( 7- inch high-brightness TFT LCD display)

* Controller: TY-UM 1 unit

* 7-inch TFT LCD display

* Current sensor: 2

*Small power supply: 1 set

Display Interface Details

图片1(14)
图片1(15)
图片1(16)
图片1(17)

DC panel cabinet

The dimensions of DC power supply system cabinet are 700(H)*500(W)*220(D)mm .

微信截图_20240617154010

Electrical Schematic for DC system

微信截图_20240617153820
Write your message here and send it to us